México - english
Wed May 23 12:48:19 2018
Wed May 23 12:48:19 2018
LINETRAXX® RCMA423

LINETRAXX® RCMA423

  • Ground-fault monitor for grounded and high-resistance grounded AC/DC systems
  • Modular installation using a single external current transformer
  • Works with AC/DC power conversion equipment including variable frequency drives
  • Digital display with real-time readings
  • Configurable Form-C (SPDT) relay contacts

The RCMA423 monitors for ground-fault current in solidly-grounded and high-resistance-grounded AC/DC (single-phase or three-phase) systems. The RCMA423 is also compatible with systems that contain power conversion equipment, such as variable frequency drives and inverters.

The pickup value is adjustable from 30 mA to 3 A (for a higher pickup value, refer to RCMA420 series). A separately configurable pre-warning alarm is also available. Three separately adjustable time delays are included - a pickup delay, startup delay, and delay on reset.

The RCMA423 provides an accurate, RMS value. Measurements are displayed in real-time via the device's on-board digital display. All device are configured using the display and push buttons. Two Form-C (SPDT) relay outputs are separately configurable to trigger on pre-warning or main alarms.

A single current transformer connects to the RCMA423 for measuring ground-fault current. A wide range of sizes are available.

  • Features
  • Applications
  • Accessories
  • Ordering information
  • Downloads
  • Ground-fault monitoring for solidly-grounded and high-resistance-grounded AC/DC systems
  • Meets or exceeds code requirements for ground-fault detection on grounded AC/DC systems, where applicable
  • Works on systems with power conversion equipment, including variable frequency drives and inverters
  • RMS measurement values
  • Digital display showing measured ground-fault current in real-time
  • Adjustable pickup value from 30 mA to 3 A
  • Connects to a single current transformer, available in a wide range of sizes
  • On-board test and reset buttons with connections for external activation
  • Adjustable time delays (pickup, startup, on reset)
  • Latching or non-latching operation
  • Two Form-C (SPDT) alarm outputs, operating normally energized (failsafe) or de-energized (non-failsafe)
  • Ground-fault monitoring on grounded and high-resistance grounded AC/DC systems
  • General power distribution
  • Motors and motor control centers
  • Generators, portable and fixed
  • Control systems
  • Heat trace systems, per NEC 427.22 and CEC 62-116
  • Battery backup systems
  • Grounded solar arrays, per NEC 690.41(B) (2017 edition), NEC 690.5 (2014 edition), and CEC 64-064(4)
  • Energy storage systems

 

Mandatory accessories for LINETRAXX® RCMA423

AC/DC current transformers
Part No.OpeningShape and TypeOrdering No.
W20AB0.78" (20mm)circular, solidB98060008
W35AB1.35" (35mm)circular, solidB98080016
W60AB2.4" (60mm)circular, solidB98080026
W120AB4.7" (120mm)circular, solidB98080041
W210AB8.25" (210mm)circular, solidB98080040

Optional accessories for LINETRAXX® RCMA423

Connection cable for use with RCMA420/423 and WAB series current transformers
Part No.LengthOrdering No.
WX-1003' (1m)B511100033
WX-2508' (2.5m)B511100032
WX-50016' (5m)B511100031
WX-100032' (10m)B511100034

Variants of LINETRAXX® RCMA423


Part No.Supply VoltageOrdering No.
RCMA423-D-116-72 VAC (42-460 Hz), 9.6-94 VDCB94043023
RCMA423-D-270-300 VAC (42-460 Hz), 70-300 VDCB94043025

Downloads for LINETRAXX® RCMA423