ISOMETER® isoPV1685 Series

ISOMETER® isoPV1685 Series

  • Ground-fault monitoring device for DC IT systems
  • Application photovoltaic systems up to DC 1500 V
  • Separately adjustable response values 200 Ω…1 MΩ
  • Automatic adaptation to the system leakage capacitance up to 2000 μF
  • Interface selectable RS-485 or Modbus

The device is used for insulation and residual current monitoring of large photovoltaic systems up to 1500 V designed as IT systems. The measurement method specially developed for slow voltage fluctuations (MPP-Tracking) monitors the insulation resistance even in systems equipped with large solar generator panels where extremely high system leakage capacitances against ground exist due to interference suppression methods. Adaptation to system-related high leakage capacitances also occurs automatically. The device generates locating current pulses required for ground-fault location. That allows the localization of the ground fault using permanently installed or mobile ground-fault locators. Integrated ground-fault monitoring allows fast signalling of a measured ground faults on the AC side (inverter, transformer).

  • Features
  • Applications
  • Accessories
  • Ordering information
  • Downloads
  • Only device versions isoPV1685PFR and isoPV1685P provide a locating current injector. The device version isoPV1685PFR additionally provides residual current monitoring!
  • Insulation monitoring of large-scale photovoltaic systems
  • Measurement of low-resistance insulation faults
  • Separately adjustable response values Ran1 (Alarm 1) and Ran2 (Alarm 2) (both 200 Ω…1 MΩ) for prewarning and alarm. Ran1 ≥ Ran2 applies.
  • Automatic adjustment to high system leakage capacitances up to 2000 μF, selectable range
  • Connection monitoring of L+, L- for reverse polarity
  • Integrated locating current injector up to 50 mA (isoPV1685P(FR) only)
  • Fast detection of insulation faults on the AC side by residual current monitoring (inverter, transformer) allowing fast disconnection (isoPV1685PFR only)
  • Residual current response values IΔn for prewarning and alarm (1…5 A) (isoPV1685PFR only)
  • CT connection monitoring (isoPV1685PFR only)
  • Device self test with automatic fault message in the event of a fault
  • Alarm relays separately adjustable for insulation faults, residual current faults and device errors (isoPV1685PFR only);
  • Alarm relays separately adjustable for insulation fault 1, insulation fault 2 (isoPV1685P, isoPV1685RTU only)
  • CAN interface to output measured values, statuses and alarms
  • RS-485 interface
    - isoPV1685(P)FR: BMS bus, e.g. to control the insulation fault location
    - isoPV1685RTU: BMS bus or Modbus (can be switched using the DIP switch)
  • μSD card with data logger and history memory for alarms

 

Variants of ISOMETER® isoPV1685 Series

Ordering information
TypeResponse value rangeSupply voltage*Art. No.
isoPV1685RTU-425200 Ω…1 MΩDC 18…30 VB91065603
isoPV1685P-425200 Ω…1 MΩDC 18…30 VB91065604
isoPV1685PFR-425200 Ω…1 MΩDC 18…30 VB91065600